L0
Call(706) 730-6113 OrBook a visit
Trace it
  1. Home
  2. Trace the complaint
Signature page

Trace the complaint down the building

A complaint arrives from one suite. The cause is on that floor about as often as it is somewhere else — on the roof, in the ceiling void, in the suite above, or in the risers. Pick what has been reported and the section lights up where to look.

One suite too hot, the next one fine

The two suites prove the plant works. Something is different about the path the air takes to the hot one, or about what that suite is doing to its own air. This is a delivery problem far more often than a capacity one, and the most common single cause is a fit-out that happened months ago in a different suite.

  1. Roof

    Which unit actually serves it

    Start by confirming that the unit everyone believes serves that suite is the one that does. In buildings that have been re-partitioned this is wrong surprisingly often. Then the ordinary checks: coil, charge, belt, and the economiser — stuck open in a Georgia summer it pulls 95°F outside air in all day and nothing inside indicates it.

  2. Void

    What changed above the ceiling

    A flexible branch crushed by a new cable tray or squashed when a ceiling was re-laid. A damper closed during someone else’s fit-out. A diffuser blanked off and forgotten. A return path blocked by a partition that was built to the slab when the rest go to the ceiling grid.

    This is where the answer usually is, and it is usually free to find and cheap to fix.

  3. Suite

    What the tenant put in it

    A server cupboard, a display fridge, a bank of monitors, a wall of west-facing glass with the blinds taken down, or twelve people in a room designed for six. None of these are faults — but they are load, and the system was sized before they arrived.

    If this is the cause, the honest answer is a supplementary unit or a change to the space, not a bigger rooftop unit for the whole building.

Cold along the outside wall in winter

A perimeter that is cold while the middle of the space is fine is an envelope and delivery problem, not a plant problem. The roof is not lit for this one, because a unit capable of heating the middle of the floor is capable of heating the edge of it.

  1. Void

    Where the warm air is being put

    In a lot of fitted-out suites the diffusers were placed for the original open plan and never moved when offices were built along the glass. Warm air delivered into the middle of a floor does not reach a perimeter that is losing heat, and no amount of extra run time changes that.

    Moving or adding a diffuser and a branch is ordinary work. So is finding that the perimeter branch exists and is closed.

  2. Suite

    The glass and the edge of the slab

    Single glazing, failed seals, an uninsulated slab edge, or a curtain-wall detail that was never much good. The complaint is real and the heating system is not the thing that is wrong.

    Where this is the cause we will say so, and it is not our work — it is a glazing or building fabric question, and putting more heat at it is the expensive way to lose the same argument every winter.

    Building fabric, not us

Smells or air arriving from another tenant

This is a pressure problem, and it is the one complaint on this page that involves the whole building at once. Air moves from where there is more of it to where there is less. If one tenant throws air out hard and nothing replaces it, that air gets pulled from everywhere else — through the ceiling grid, under doors, up stairwells and through every gap in a demising wall.

  1. Roof

    Extract against make-up air

    Find every extract fan on the roof and find what is replacing the air it removes. A restaurant, a salon or a nail bar can extract several thousand cubic feet a minute; if the make-up air unit is absent, undersized or switched off, the building is being emptied.

    This is also, by a long way, the most common reason a flue misbehaves in a shared building.

  2. Void

    The path between the suites

    Demising walls that stop at the ceiling grid instead of going to the slab. A shared return plenum. A duct that crosses from one tenancy into another because the layout changed. Once the building is in depression, every one of these becomes a route.

  3. Suite

    What the receiving suite is doing

    A suite with no extract of its own, doors kept shut, and a system on setback out of hours will sit at the lowest pressure in the building and collect whatever the others are pushing out.

  4. Below

    The source, which is usually downstairs

    Kitchens, salons and workshops are normally at ground level, and the air they throw out has to come from somewhere. Measuring the pressure difference across the demising line settles who is doing what, and it is the only thing that ends this argument between tenants.

Noise or vibration through the ceiling

New noise is almost always mechanical wear or a mounting that has let go. None of it is urgent on the day and all of it is cheaper before the thing attached to it fails. It is also the complaint most likely to be reported by whoever sits directly under it and ignored by everyone else.

  1. Roof

    Bearings, wheels and isolators

    A fan bearing on its way out, a fan wheel out of balance, or a vibration isolator that has perished and is now transmitting straight into the curb and down into the structure. A rattle is usually a panel or a guard; a hum you feel rather than hear is nearly always a mount.

  2. Void

    Ductwork and hangers

    Ducts drumming at a joint, a flexible connector that has gone hard, or a hanger that has worked loose and is now letting a run rest on a ceiling grid. All ordinary, all cheap, and all much easier to find with somebody standing in the suite while somebody else is in the void.

  3. Base

    Pumps, risers and other trades

    Worth ruling out before anybody spends money on the roof: a circulating pump, a booster set, a lift motor room or a compressor belonging to a tenant can all transmit through a structure and arrive several floors away sounding like an air conditioning fault.

    Two of those are not ours, and we would rather identify that than replace a bearing that was never the problem.

    Sometimes another trade

A water stain on the ceiling

Two candidates, and they are dealt with by two different trades. Telling them apart is usually quick, and getting it wrong is expensive — a roof repaired when the problem was a condensate drain will simply stain again in a fortnight.

  1. Roof

    The curb, the flashing and the membrane

    If the stain follows rain, and it is near or downhill of a unit, the curb or the flashing round the penetration is the first suspect. Standing water beside a unit makes this far more likely and is itself a roof problem, not a plant one.

    The repair belongs to whoever looks after the roof. We will lift and reset a unit so the work can be done properly, and doing it in the wrong order means paying twice.

    Roofer, with us to lift
  2. Void

    Condensate, and it usually is

    If the stain appears in the cooling season regardless of weather, it is almost certainly condensate: a blocked drain, a dry or missing trap, a corroded pan, or a secondary pan that has been quietly catching water for a year and has now filled.

    This is ours, it is a small job, and it gets considerably larger if it is left through a season.

Nobody knows which unit serves what

Not a fault, but it is the reason everything else on this page takes twice as long. When nobody can say which unit serves which suite, every call-out begins with somebody switching things off to find out — usually during trading hours, usually in front of a tenant.

  1. Roof

    Tag it, once

    Every unit numbered and labelled, matched to the suite or area it serves and to the plate data recorded off it. Half a day on most buildings, and it is the cheapest thing we ever do.

    It also produces the real age of every unit on the roof, which changes budget conversations immediately and occasionally changes a sale.

  2. Base

    Disconnects, meters and who is paying

    Which disconnect isolates which unit, which meter it runs through, and whether the way the building is actually wired matches the way the leases say it is billed. We record what we find.

    What is due under a particular lease is a question for you and your attorney, not for us — but you cannot answer it without knowing which unit is on which meter, and that part we can settle.

    Lease terms are not ours
What this page is not It is a way of describing a complaint accurately before anybody drives out, not a diagnosis. Nothing here asks a tenant or a manager to open a unit, go onto a roof unaccompanied, or lift anything. And it gives no prices, because the same sentence describes a half-hour job and a two-day one depending on the building.
On the phone
Four things that halve the call

What to have ready

Which suite, and which unit

By its tag if it has one, or by what it serves. If the building has never been tagged, say so — that is useful information on its own.

When it started

And what else happened around then. A fit-out two suites away, a ceiling re-laid, a new tenant with a kitchen. The date is often the whole diagnosis.

Whether it follows the weather

Rain, heat, cold, or none of them. It is the single fastest way to separate a roof problem from a condensate problem from a load problem.

What it stops

Whether the tenant can trade without it today. It decides where you go in the day, and we would rather be told than assume.